  • Thumbnail Image
    Item
    Power transformer differential protection for three Eskom feeders
    (IEEE, 2022-08-22) Ngema, Philani N.; Davidson, Innocent Ewaen; Buraimoh, Elutinji
    Differential protection's purpose is to offer phase fault protection that is both quicker and more discriminative than that provided by basic overcurrent relays. Transformer differential protection is the primary protection against earth faults and phase-to-phase faults. CTs on the HV side are counterbalanced by CTs on the LV side. There are a variety of distinct connections, but there are a few key considerations that apply to every design. This sort of protection continually monitors and compares the current flowing between CTs (in this example, HV and MV CTs) inside a protected zone. The following are the primary requirements of this protection, Highest sensitivity, Load stability over the whole tap range, Stability in through-fault circumstances, Stability for magnetizing inrush with associated DC offset decay, when a zone fault is identified, simultaneously opens both HV and MV breakers.
  • Thumbnail Image
    Item
    Performance evaluation of percentage differential relays on power transformer and reliability assesment in HVDC grid protection scheme
    (IEEE, 2022-08-22) Ngema, Philani; Davidson, Innocent Ewaen; Buraimoh, Elutunji
    Percentage differential relays remain the most sensitive protection tool applied as backup protection on power transformers, busbar, and generators. Relays sometimes do mis-operate with the current transformer being affected by external fault leading to saturation, and the subsidence current present after clearing external faults. The cause of misoperation of percentage differential relays cannot be ignored that it entirely depends on magnitudes more than directionality for tripping decisions. This paper covers evaluating differential element performance, analysis of transformer inrush current, internal faults, external faults, and overexcitation conditions. The accurate computing of current transformers is also included. This protection only applies to 10MVA and above on transformers; however, it is not limited to transformers, but also transmission lines, busbars, and generators. The balance of the paper is on reliability assessment based on the HVDC grid protection scheme operation